* Channels 4 voltage, 63~600V (isolated). 4 current 0 to 3kA (3ph and neutral) RM
* Supplied with 4 dual range (500A or 3000A), flexible clamp-on CT's (length 600mm and diameter 190mm)
* Clamp-on CT's of 100A and 200A also available
* Memory: 8GB
* Colour LCD display, 480 x 272 Graphic TFT
* Built-in GPS
* 2 probes supplied to monitor temperature, range: -50℃ to 150℃
* Records: V, A, pf, f(Hz), kVA, kVAr, kW, harmonics, Inter harmonics, voltage and current imbalance (THD and individual to 50th), Flicker, total energy, tariffs, maximum demands, and transient and sub-cycle disturbances
* Monitors mains signalling (Ripple amplitude) and IEC events (sags, swells, dips, interruptions, RVC)
* Records DC voltages and also DC currents with DC clamps (separately available)
* A PC is required with the CHK Citrus software (supplied) to configure this unit before operating.
* Download data, clear memory and configure the device with no interruption to logging
* Graphical display of logged data with ability to drill down as required. Export data to Excel or generate pdf reports