Apart from the variable frequency VLF output, the operator can also select dual polarity DC and cable jacket or sheath testing outputs modes. The applied test voltage, current, capacitance, resistance and time are displayed and recorded. The instrument is easily programmable allowing the operator to setup or select test sequences in either automatic or manual mode. High voltage power source suitable for testing electrical plant including cables: XLPE, PE, EPR, PILC etc, capacitors, switchgear, transformers, rotating machines, insulators and bushings.
True sine wave low frequency output. The HVA60 is capable of testing 1µF (Approx. 10,000 ft/ 3000m of cable) at 0.1Hz and 60kV peak. The frequency of the output can also be reduced allowing even larger capacitance loads to be tested. At 0.02Hz, approx. 50,000 ft/15,000m of cable can be tested. Complies with CENELEC, IEEE400.2, VDE 0296 and other international standards.