10kV Insulation Resistance Meter designed for the testing and maintenance of high voltage equipment including single- and multi-core cables, transformers, motors and generators, capacitors, switches etc. Meets EN 61010-1 and IEC 61557 standards. Also offers a cable “thumper” like feature to intensify the damage for fault finding.
- Pre-set standard test voltages: 50, 100, 250, 500 V, 1, 2.5, 5 and 10 kV
- User defined test voltage: 50 to 1kV - 10V steps; 1 kV to 10 kV in 25 V steps
- Maximum measuring range: 40 TΩ
- Test current: 1.2 mA, 3 mA or 6 mA
- Continuous indication of measured insulation resistance or leakage current
- Displays capacitance during the measurement of RISO
- Pre-configured diagnostic tests include: Polarization index (PI), absorption coefficients Ab1, Ab2 and dielectric absorption ratio (DAR) measurement, Step voltage insulation resistance (SV), Dielectric Discharge calculation (DD)
- Temperature measurement: -40 to 100°C with ST-1 probe included
- Safety rated up to Cat IV 600 V (III 1000 V)
- Graphical LCD 5.6" display with data transmission via USB and Bluetooth
- Memory: 8 MB equivalent (10,000 records)
- Operates from battery (1,000 measurements) or mains supply
Additional Feature:
- Damage location (burnout) – cable “thumper” like feature to intensify the point of cable damage
- Pinpoint the fault location through use of separate time domain reflectometric method, see Megger 2000-3P